1、 Definition of centrifugal fan
The centrifugal fan is a driven fluid machine that relies on the input mechanical energy to increase the gas pressure and discharge gas. Centrifugal fans are widely used in oil plants, mainly including: 1. ventilation and dust removal: used for oil cleaning, meal/skin crushing, and ventilation and dust removal during oil/meal transportation; 2. Pneumatic transportation: such as the wind transportation of bean skin, the transportation of clay, the wind separation of skin/kernel, and the transportation of coal ash; 3. Ventilation and drying: such as induced air of conditioning tower, drying/cooling of expanded materials, drying/cooling of meal, etc.
2、 Principle of centrifugal fan
When the impeller rotates with the shaft, the gas between the blades will also obtain inertial centrifugal force with the impeller rotation, and the gas will be thrown out from the outlet between the blades. The thrown gas is squeezed into the casing, so the gas pressure in the casing increases and is finally directed to the outlet for discharge. After the gas is thrown out, the pressure in the central part of the impeller decreases. The external gas can be inhaled from the suction port of the fan through the hole in the center of the front disc of the impeller, and the gas can be continuously transmitted.
3、 Structure of centrifugal fan
The centrifugal fan is mainly composed of impeller, casing, air inlet, regulating damper and driving device.
Impeller: composed of front disc, rear disc and blades installed between two discs;
Casing: the casing of the fan is volute shaped, welded with thin steel plates, which is used to collect the gas from the impeller and make it smoothly led to the outlet of the fan along the direction of impeller rotation, and pressurize the gas;
Air inlet: the head part of the suction pipe section, which plays the role of gas gathering, is also called a collector.
4、 Main performance parameters
Flow Q: the amount of fluid transported by the fan in unit time, usually expressed by volume flow, in m3/s or m3/h, related to the structure, size and speed of the fan;
Pressure head p: effective energy provided by fan for unit volume flow, in pa;
efficiency η: During the actual operation of the fan, due to various energy losses
The actual (effective) head and flow are lower than the theoretical value, while the input power is higher than the theoretical value. The parameter reflecting the magnitude of energy loss is called efficiency. The efficiency is related to the type, size, processing accuracy, gas flow and nature of the fan. Generally, the efficiency of small fans is 50%~70%, while that of large fans can reach 90%;
Shaft power N and effective power Ne: shaft power is the power of motor input fan shaft, in W or kW. The effective power of centrifugal fan refers to the energy obtained by the gas from the impeller in unit time, so there are Ne=Qp, N=Ne/ η= Qp/ η。
Rotating speed n: the number of revolutions per minute of fan and fan impeller, namely "r/min".
5、 Use and operation of fan
5-1. Preparation before fan startup
1) Close the regulating damper and the inlet and outlet damper of the fan;
2) Manually turn the gear, check the clearance of all parts of the fan, and turn the impeller and casing to see if there is friction;
3) The coupler and pulley protection passport are installed in place;
4) Whether the oil level of the bearing housing meets the lubricating oil level during operation;
5) For fans with water cooling bearings, check whether the water supply of the cooling water pipe is good;
6) The rotation direction of the fan shall be determined electrically, and water and oil leakage, vibration, abnormal noise and odor shall be checked.
5-2. Startup of fan
1) Start the fan (pay attention to whether the operation is stable);
2) After the fan is started, gradually open the air damper until the actual production air volume is required; When opening the damper, pay attention to the running current of the motor to prevent the fan from overloading due to excessive opening of the damper;
3) After startup, the bearing temperature of the fan shall be tested, and the bearing temperature rise shall not exceed 40 ℃ of the ambient temperature on site;
5-3. Inspection of fan during operation
1) Listen to whether the fan operates stably, whether there is abnormal sound or friction;
2) Check whether all anchor bolts are loose;
3) Check the temperature and lubrication of the bearing;
4) Whether the cooling water of bearing lubricating oil is unblocked and whether there is temperature difference in the inlet and outlet pipes;
5) Whether the bearing box has lubricating oil leakage;
6) Whether the bearing box and bearing have abnormal noise and rotate smoothly;
7) Check whether the current operation is stable;
5-4. Emergency stop
1) The fan is found to have violent noise;
2) The impeller has friction with the casing;
3) The casing vibration suddenly increases;
4) The bearing temperature rises continuously and exceeds the allowable temperature rise range;
5) The sudden rise of current cannot be recovered within 2 minutes;
6) Serious oil leakage of bearing box;
7) The cooling water is interrupted for more than half an hour.
5-5. Fan shutdown
1) Now stop the fan after reducing the load;
2) Close the inlet and outlet valves of cooling water;
3) If the hot air is transported, the fan shall be stopped after the heater is stopped until the outlet air temperature of the fan decreases to 40 ℃;
4) After the fan is shut down, open the drain valve at the bottom of the casing for drainage; At the same time, close the inlet and outlet damper of the fan.